Home / Regular Issue / JST Vol. 25 (S) Jul. 2017 / JST-S0342-2017

 

Synchronisation of Output Voltage Waveforms in Phase Synchronous inverter with LCL Filter for Smart Grid Systems

Tawfikur Rahman, M. I. Ibrahimy and S. M. A. Motakabber

Pertanika Journal of Science & Technology, Volume 25, Issue S, July 2017

Keywords: Choke coil, controller, LCL filter, PSI, transformer

Published on: 28 Feb 2018

A new smart grid system is widely used for energy supply system because it is simple, available, low cost, high efficiency and environmentally friendly. Conventionally, inverter techniques are utilised to convert input DC into output AC with the same frequency and phase. This process suffers the same problem which is a higher harmonic distortion, phase synchronisation, lower quality of waveform and long distance, among others. In this paper, three phase synchronous inverters (PSI) were used to direct synchronous PWM control, LCL filter, three phase RLC load, three phase Yg-Delta transformer, 5 km feeder with 2 MW load. PWM was used to generate the pulse signal for synchronisation. However, LCL filters were used to remove the noise in inverter output and transformer output side of the design. A balanced three phase load (10 kVAR) and also the input DC voltage 500 V were considered in this design. Three phase transformer (100kVA/260V/25kV) was used to increase the inverter output voltage and current with the fundamental frequency (50 Hz). The system conversion efficiency was 99.96% and phase synchronous error for each phase was approximately 4.5 degrees.

ISSN 0128-7680

e-ISSN 2231-8526

Article ID

JST-S0342-2017

Download Full Article PDF

Share this article